Change Summary
NEC® Text |
---|
Copyright© 2013 National Fire Protection Association (See NEC for complete text) |
Leviton Comment
Articles 820.24, 770.24, 820.24 and 830.24 were grouped together because the intent of these articles is very much the same (low smoke cable accessories in plenum areas). This grouping makes for a quicker and more user-friendly read of this Pocket Guide. However there are some variances in text. Please reference the 2014 NEC Text for exact language.
Expert Analysis
The NFPA Standards Council has assigned primary responsibility for combustibles, located within air handling spaces, to the Technical Committee on Air-Conditioning and the Standard, NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems. Presently, NFPA 90A-2012 has requirements for cable ties in ceiling cavity plenums located in 4.3.11.2.6.5 and for raised floor plenums located in 4.3.11.5.5.6. Both of these sections require that all electrical equipment with combustible enclosures, including their assemblies and accessories, cable ties, and other discrete products, shall be permitted in the ceiling cavity plenum and raised floor plenums only where listed according to ANSI/UL 2043, Standard for Safety Fire Test for Heat and Visible Smoke Release for Discrete Products and Their Accessories Installed in Air-Handling Spaces. These air-handling spaces are called “Other Spaces Used for Environmental Air (Plenums)” in NEC 300.22(C). To comply with NFPA 90A, CMP-16 approved a new last sentence be added to 800.24 (and to 770.24, 820.24 and 830.24) requiring nonmetallic cable ties and other nonmetallic accessories to be listed as having low smoke and heat release properties. This action, and the action in 300.22(C)(1), brings the NEC in compliance and correlation with NFPA 90A.