Change Summary
NEC® Text |
---|
Each sign and outline lighting system, feeder circuit or branch circuit supplying a sign, …(See NEC text)… Copyright© 2013 National Fire Protection Association (See NEC for complete text) |
Expert Analysis
The substantiation for this change points to a need for additional electrical safeguards for sign workers. In reality, sign supply conductors are often installed within a sign enclosure and run to the supply side of the randomly located disconnect mounted on the sign. These line-side supply conductors located within the sign enclosure remain energized whether or not the sign disconnect is turned off. Only the conductors from the load-side of the sign disconnect to the sign supply terminals are de-energized when the disconnect is opened. This practice exposes sign worker(s) to serious electrical hazards. Previous installation requirements did not specifically require all ungrounded conductors to be de-energized before entering a sign body or enclosure. Now, this new requirement of 600.6(A)(1) specifically requires the disconnecting means to be located at the point the feeder circuit or branch circuit(s) supplying a sign enters the sign enclosure or a supporting pole. Furthermore, the disconnecting means must disconnect all wiring where it enters the enclosure of the sign or pole. However, a practical and limited exception provides latitude to permit energized conductors within a sign only if they are installed using a Chapter 3 wiring method.
Outdoor Switching
Leviton offers a unique solution for outdoor switching with catalog number COVER-S. This switch cover can actuate any traditional 15A-40A Toggle switch including Manual Motor Starters.